Short description
I/O module 8 digital outputs for switching electromechanical loads, current monitoring, switching instant detection, pulse width modulation
General information
B&R ID code 0x1D43
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Outputs Yes, using LED status indicator and software (output error status)
Power consumption
Bus 0.01 W
Internal I/O 1 W (Rev. ≥G0), 1.5 W (Rev. <G0)
External I/O Corresponding to external load
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
KC Yes
Digital outputs
Nominal voltage 24 VDC
Nominal output current 0.6 A
Total nominal current 4.8 A
Connection type 1-wire connections
Output circuit Sink
Output protection Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads
Pulse width modulation
Period duration 1 ms (1 kHz) or 20 µs (50 kHz)
Pulse duration 0 to 100%
Resolution for pulse duration 1%
Inrush current Max. 2 A for max. 25.5 ms
Braking voltage when switching off inductive loads 39 VDC
Reverse polarity protection No (must be protected externally)
Output voltage
Minimum 18 VDC
Nominal 24 VDC
Maximum 42 VDC
Protective circuit
External 24 VDC power supply - maximum current 10 A (melting fuse)
Electrical properties
Electrical isolation Bus isolated from channel and internal I/O power supply
Channel not isolated from channel and internal I/O power supply
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 60°C (Rev. ≥ G0), 0 to 55°C (Rev. < G0)
Vertical mounting orientation 0 to 50°C
Derating -
Storage -25 to 70°C
Transport -25 to 70°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch 12.5+0.2 mm
Materialnummer:
X20CM8323
Beskrivning:
  • 8 digital outputs
  • Current trace
  • Switching time detection
  • Pulse width modulation

The module has digital outputs for switching electromechanical loads (e.g. valves, relays) and additional functions.

Obligatoriska tillbehör
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O power supply connected through
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O power supply connected through
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Automation Studio HW uppdateringar Version (datum) Ladda ner
V2.6 HW Upgrade (X20CM8323) EXE / 606 KB
V2.6 HW Upgrade (X20CM8323) EXE / 2 MB
V3.0 HW Upgrade (X20CM8323) EXE / 605 KB
V3.0 HW Upgrade (X20CM8323) EXE / 3 MB
V4.0 HW Upgrade (X20CM8323) EXE / 2 MB
Certifikat Version (datum) Ladda ner
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
Safe cutoff of potential groups PDF / 211 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Dokumentation Version (datum) Ladda ner
Data sheet X20CM8323 PDF / 1 MB
Installation- / EMC-Guide PDF / 20 MB
X20 Package leaflet ATEX/CSA PDF / 2 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Electro eller EPLAN mallar) Version (datum) Ladda ner
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. mallar) Version (datum) Ladda ner
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Välj land och språk