Short description
I/O module | X20 energy measurement and synchronization module |
General information
Digital outputs
Quantity | 5 |
Variant | Current-sourcing FET |
Nominal voltage | 24 VDC |
Switching voltage | 24 VDC -15% / +20% |
Nominal output current | 0.1 A |
Total nominal current | 0.5 A |
Connection type | 1-wire connections |
Output circuit | Source |
Output protection | Thermal shutdown in the event of overcurrent or short circuit |
Diagnostic status | Output monitoring with 10 ms delay |
Leakage current when the output is switched off | 5 μA |
Residual voltage | <0.3 V at 0.1 A nominal current |
Peak short-circuit current | <2 A |
Switch-on in the event of overload shutdown or short-circuit shutdown | Approx. 10 ms, depends on the module temperature |
Switching delay | |
0 → 1 | <300 μs |
1 → 0 | <300 μs |
Switching frequency | |
Resistive load | Max. 100 Hz |
Insulation voltage between channel and bus | 500 Veff |
Relay outputs
Analog input voltage
Analog input current
Electrical properties
Electrical isolation |
Bus isolated from I/O power supply and digital inputs and outputs Digital inputs and outputs isolated from each other
|
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 2x terminal block X20TB12 separately. Order 2x screw clamp terminal block TB3102 and 2x screw clamp terminal block TB3104 separately. |
Pitch | 87.5+0.2 mm |
Materialnummer:
X20CM0985-02Beskrivning:
- Energy measurement for 120 to 480 VAC
- Simultaneous measurement of 2 AC power systems plus 2 additional voltages
- For multifunction measurement tasks
- Intelligent power system synchronization unit
- Current values of generator voltage and current
- Monitor functions per current power system guidelines
The module combines a power measurement module with special features in a compact footprint together with a synchronizing unit that meets all requirements.
The measurement unit is 3 current inputs are suitable for both X: 1 A and X: 5 A current transformers. Overcurrent resistance and the high resolution of the unit of measurement round off its features. For the voltage inputs, the value range can also be configured between 480 VAC and 120 VAC without any loss in converter resolution.
The area of application includes 4-wire AC power systems with a line-to-line voltage up to 480 VAC and 3-wire systems, where L2 can be grounded (V circuit). In addition, the module masters the measuring principle of the Aron circuit.
The resulting measured values range from the pure phase current and line-to-line or phase voltage to active, reactive and apparent power components, mains frequency, power factor and much more. In addition, peak values and energy meters are stored on the module in nonvolatile memory. Depending on the configuration, it is also possible to use a digital output as a pulse encoder for an external energy meter.
The synchronization unit does not just take the phasing and phase voltage into consideration; integrated intelligence also monitors the rate of change and other parameters, allowing them to influence when the synchronization output is switched. It is also possible to monitor a generator using a large number of additional conditions. A total of 4 voltage inputs provide substantial overall flexibility.
Monitoring functions expand the features of the module. Dependent overcurrent monitoring is included, which utilizes the thermal capacity of the motor/generator to allow short overloads while still providing full protection. The dependent, delayed imbalanced load monitoring used to protect three-phase generator and three-phase networks from imbalanced load can be adapted to the characteristics of different generator types using parameters while taking their special thermal time constants into account.
Obligatoriska tillbehör
Terminal blocks
0TB3102-7011 | Accessory terminal block, 2-pin, A-coded, screw clamp terminal block 6 mm² |
0TB3102-7012 | Accessory terminal block, 2-pin, B-coded, screw clamp terminal block 6 mm² |
0TB3104-7011 | Accessory terminal block, 4-pin, A-coded, screw clamp terminal block 6 mm² |
0TB3104-7012 | Accessory terminal block, 4-pin, B-coded, screw clamp terminal block 6 mm² |
X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Automation Studio HW uppdateringar | Version (datum) | Ladda ner |
---|---|---|
V4.2 HW Upgrade (X20CM0985-02) | EXE / 4 MB |
Certifikat | Version (datum) | Ladda ner |
---|---|---|
EU Declaration ATEX X20 | PDF / 218 KB | |
EU Declaration of conformity PLC X20 | PDF / 169 KB | |
UK Declaration PLC X20 | PDF / 151 KB |
Dokumentation | Version (datum) | Ladda ner |
---|---|---|
Data sheet X20CM0985-02 | PDF / 2 MB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X20 System User´s Manual | PDF / 7 MB |
E-CAD (Electro eller EPLAN mallar) | Version (datum) | Ladda ner |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD (Mechan. mallar) | Version (datum) | Ladda ner |
---|---|---|
3D data DXF / STEP X20CM0985 | ZIP / 1 MB |