Short description
Hub 2 Fast Ethernet interfaces for fiber optic cables for redundant wiring
General information
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator
Bus function Yes, using LED status indicator
Power consumption 2.3 W (rev. <D0: 2.8 W)
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
KC Yes
Interfaces
Type Active hub expansion module
Variant 2x female duplex LC
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-FX
Half-duplex Yes
Full-duplex No
Autonegotiation No
Auto-MDI/MDIX No
Hub propagation delay 0.96 to 1 µs
Wave length
Typ. 1300 nm

Rx range: 1270 to 1380 nm

Tx range: 1270 to 1380 nm
Cable fiber type Multimode fiber with 62.5/125 µm or 50/125 µm core diameter
On both sides: Male duplex LC connector
Optical power budget
Glass fiber 62.5/125 µm, NA = 0.275 11 dB
Glass fiber 50/125 µm, NA = 0.200 7.7 dB
Line length
Half-duplex Max. 400 m between 2 stations (segment length)
POWERLINK Max. 2 km between 2 stations (segment length)
Electrical properties
Electrical isolation Power supply isolated from Ethernet (IF1 and IF2)
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation (with ≥2 hubs) -25 to 50°C (Rev. <D0: 0 to 40°C)
Vertical mounting orientation (with ≥2 hubs) -25 to 35°C (Rev. <D0: 0 to 35°C)
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Slot Hub expansion for X20BC8084 and X20HB8884
Número do material:
X20HB2886
Descrição:
  • Active hub expansion module
  • 2x 100 BASE-FX hub for redundant wiring
  • Hot-swap-capable

The X20BC8084 POWERLINK bus controller and the X20HB8884 module are equipped with an integrated link selector function. An additional 1 or 2 slots are available, depending on the bus base used. The active X20HB2886 hub expansion module can be operated in these slots. Note that the hardware revision of the X20BC8084 and the X20HB8884 must be ≥E0.

The active hub expansion module is equipped with one integrated 2x hub and allows redundant wiring. This means that the connection between the two 100 Base-FX interfaces remains intact if there is a failure in the bus controller or Compact Link Selector. The Ethernet connection is made using 62.5/125 μm or 50/125 µm fiber optic multimode cable with a duplex LC connection. The status of the module and network are indicated by LEDs.

Outras informações:

Technology information: Redundância

User's manual: Redundancy for control systems

Acessórios obrigatórios
Expandable bus controllers
X20BC8084 X20 bus controller, 1 POWERLINK interface, 1x link selector for POWERLINK cable redundancy, supports expansion with active X20 hub modules, 2x RJ45, order bus base, power supply module and terminal block separately!
System modules for expandable bus controllers
X20BB82 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, with 2 expansion slots for 2 X20 add-on modules (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20 redundancy systems
X20HB8884 X20 Compact link selector, 2x RJ45, order bus base, power supply module and terminal block separately!
Atualizações de HW Automation Studio Version (Data) Download
V4.0 HW Upgrade (X20HB2886) EXE / 827 KB
Certificados Version (Data) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Documentação Version (Data) Download
Datasheet X20(c)HB2886 PDF / 151 KB
Installation- / EMC-Guide PDF / 20 MB
Redundancy for control systems PDF / 9 MB
X20 Package leaflet ATEX/CSA PDF / 2 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Modelos Electro ou EPLAN) Version (Data) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. Modelos) Version (Data) Download
3D File DXF/STEP X20 system module X20(c)HB288x ZIP / 1 MB

Por favor escolha o país e o idioma

B&R Logo