General information
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
Terminal block
Number of pins 12
Type of terminal block Push-in terminal
Push-in force per contact Typ. 10 N
Cable type Only copper wires (no aluminum wires!)
Wire stripping length 7 to 9 mm
Connection cross section
Single-wire 0.08 to 1.50 mm² / 28 to 16 AWG
Fine-stranded wires 0.25 to 1.50 mm² / 24 to 16 AWG
With wire end sleeve 0.25 to 0.75 mm² / 24 to 20 AWG
Distance between contacts
Left - Right 4.2 mm
Above - Below 8.25 mm
Terminal temperature compensation 2x Pt1000 integrated in the terminal
Electrical properties
Nominal voltage 24 VDC
Max. voltage 50 VDC
Nominal current 2 A / contact
Contact resistance ≤5 mΩ
Ambient conditions
Temperature
Operation Corresponds to the X20 module used
Relative humidity
Operation Corresponds to the X20 module used
Materiaalnummer:
X20TB1E
Omschrijving:
  • Integrated terminal temperature compensation
  • Tool-free wiring with push-in technology
  • Simple wire release using a screwdriver
  • Ability to label each terminal
  • Plain text labeling also possible
  • Test access for standard probes
  • Can be customer-coded

The X20TB1E terminal block is equipped with two integrated PT1000 sensors. It is therefore optimally suited for internal terminal temperature compensation.

Graag land en taal kiezen

B&R Logo