General information
B&R ID code | 0x1AC9 |
Status LED |
Yes (color / blink code) 24 VDC OUT power supply (DCOK LED) = Yes |
Status indicators | Operating status and power supply |
Diagnostics | |
Power supply |
24 VDC OUT: Yes, using LED and software 24 VDC X2X: Yes, using software |
X2X Link | Yes, using software |
Overload | Yes, using software (outputs) |
Input capacitance | |
Module power supply | 220 µF |
Power consumption | Max. 0.75 W |
Electrical isolation | |
Digital outputs - 24 VDC X2X, OUT power supply | No |
X2X Link - 24 VDC X2X, OUT power supply | Yes |
X2X Link - Digital outputs | Yes |
Remote valve terminal connection for 25-pin DSUB multi-pin connection | 16 valves |
Certifications | |
CE | Yes |
UKCA | Yes |
UL |
cULus E115267 Industrial control equipment |
Circuit
Bus connection | 10-pin |
GND pin | 22, 23, 24, 25 |
Power supply | via bus connector |
Interfaces
User interface | |
Variant | 10-pin male multipoint connector |
Type | X2X Link slave |
Digital outputs
Switching voltage | 24 VDC ±25% |
Total nominal current | 1.6 A |
Output circuit | Source |
Output protection | Protected against short circuit, overload and overtemperature |
Switching delay | |
0 → 1 | Typ. 150 μs / max. 200 μs |
1 → 0 | Typ. 175 μs / max. 250 μs |
Type | High-side driver (source) |
Max. output current | 0.1 A |
Max. switching frequency | 100 Hz |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | 0 to 55°C |
Storage | -20 to 70°C |
Transport | -20 to 70°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order 1x terminal block TB710 separately. |
Installation | 25-pin DSUB, screw mounting, 4-40 UNC |
Weight | 56 g |
Module dimensions including mounting plates | 63 x 59 x 20 mm (H x W x D) |
Référence produit:
7XV116.50-01Description:
Remote valve terminal connection, 16 digital outputs, 0.1 A, 24 VDC, for 25-pin DSUB multipin connector, GND pins 22, 23, 24, 25, X2X Link, electrically isolated, common 24 VDC power supply, order 1x terminal block 0TB710.91 separately!
Accessoires obligatoires
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V4.0 HW Upgrade (7XV116.50-01) | EXE / 724 Ko |
Certifications | Version (date) | Téléchargement |
---|---|---|
Safe cutoff of potential groups | PDF / 211 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Compact I/O User's Manual | PDF / 4 Mo | |
XV Users's Manual | PDF / 4 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D data DXF / STEP XV IP20 | ZIP / 2 Mo |