Short description
I/O module | IO-Link master with 4 IO-Link interfaces |
General information
B&R ID code | 0xF9F7 |
Status indicators | - |
Diagnostics | |
Module run/error | Yes, using software status |
Power consumption | |
Internal I/O | 0.6 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
Sensor/Actuator power supply
Voltage | I/O power supply minus voltage drop for short-circuit protection |
Voltage drop for short-circuit protection at 0.3 A | Max. 0.3 V |
Power consumption | Max. 12 W per IO-Link interface |
Short-circuit proof | Yes |
Overload protection | |
Switch-off delay | Configurable using software |
Switch-off duration | Configurable using software |
IO-Link in master mode
Transfer rates | |
COM1 | 4.8 kbaud |
COM2 | 38.4 kbaud |
COM3 | 230.4 kbaud |
Limit values for COM3 | |
Max. connection capacity | 22 nF (cable + IO-Link device) |
Max. load | 96 Ω / 250 mA |
Data format | 1 start bit, 8 data bits, 1 parity bit (even), 1 stop bit |
Bus level | 24 VDC (active), 0 VDC (resting voltage) |
IO-Link in master mode or in SIO mode "digital output"
Variant | Bipolar, positive and negative switching |
Peak short-circuit current | <1.3 A |
Residual voltage | <0.7 VDC at nominal current 0.25 A |
Switching voltage | I/O power supply minus voltage drop for short-circuit protection and semiconductor switch |
Voltage drop on semiconductor switch | Max. 0.44 VDC at 0.2 A |
Switching frequency |
Typ. 25 kHz 300 kHz in IO-Link master mode |
Switching delay | |
0 → 1 | <1 µs |
1 → 0 | <1 µs |
Switch-on in the event of overload shutdown or short-circuit shutdown | Configurable with software |
IO-Link in SIO mode "Digital output"
IO-Link in SIO mode "digital input"
Nominal voltage | 24 VDC |
Input characteristics per EN 61131-2 | Type 1 |
Input filter | |
Hardware | 220 ns |
Software |
3 µs (without glitch filter) 4.2 µs (with glitch filter) |
Input circuit | Sink |
Input voltage | 24 VDC -15% / +20% |
Input current at 24 VDC | Typ. 5.8 mA |
Input resistance | Typ. 4.14 kΩ |
Switching threshold | |
Low | <5 VDC |
High | >15 VDC |
Electrical properties
Electrical isolation |
Bus isolated from IO-Link IO-Link not isolated from IO-Link |
Ambient conditions
Temperature | |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 100%, condensing |
Storage | 5 to 100%, condensing |
Transport | 5 to 100%, condensing |
Mechanical properties
Dimensions | |
Width | 47 mm |
Length | 95 mm |
Material number:
X90DSI00.04-00Description:
- 18 to 30 VDC
- 4 IO-Link devices
- 4 digital channels, can be used as inputs or outputs
- Sensor/actuator power supply
- NetTime timestamps: IO-Link data
- X2X Link
The DS option board is an IO-Link master that allows intelligent sensors and actuators to be connected per the IO-Link standard. Communication to the mainboard is made possible via X2X Link.
Automation Studio HW Upgrades | Version (Date) | Download |
---|---|---|
V4.7 HW Upgrade (X90DSI00.04-00) | EXE / 3 MB |
Certificates | Version (Date) | Download |
---|---|---|
EU Declaration Industrial sector X90 | PDF / 163 KB | |
EU Declaration Mobile machinery X90 | PDF / 146 KB | |
UK Declaration Industrial sector X90 | PDF / 110 KB | |
UN ECE-R10 | PDF / 382 KB |
Documentation | Version (Date) | Download |
---|---|---|
Data sheet X90DSI00.04-00 | PDF / 1 MB | |
X90 mobile System User´s Manual | PDF / 49 MB |
E-CAD (Electro or EPLAN Templates) | Version (Date) | Download |
---|---|---|
Makro-/Artikeldaten 4.0.1 (X90DSI00.04-00) | EXE / 946 KB | |
X90 EPLAN P8 from V2.4 | EXE / 69 MB |