Short description
Bus module X2X+ bus module, not mechanically keyed, internal I/O power supply connected through
General information
B&R ID code 0xF378
Power consumption
Bus 0.45 W
Internal I/O -
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
I/O power supply
Nominal voltage 24 VDC
Permissible contact load 10 A
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 50°C
Vertical mounting orientation -25 to 45°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Pitch 12.5+0.2 mm
Material number:
X20BM11X
Description:
  • Bus module for 24 VDC I/O modules
  • The internal I/O power supply is connected through.

The X2X+ bus module serves as the basis for all single-width electronics modules. The internal I/O power supply is connected through.

Automation Studio HW Upgrades Version (Date) Download
V4.7 HW Upgrade (X20BM11X) EXE / 1 MB
Certificates Version (Date) Download
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
UK Declaration PLC X20 PDF / 151 KB
Documentation Version (Date) Download
Data sheet X20BM11X PDF / 112 KB
Installation- / EMC-Guide PDF / 20 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB

Please choose country and language

B&R Logo